GMP车间净化公司净化空调设计

来源:http://www.henganjh.cn │ 发表时间:2019-05-27 

  GMP车间净化公司净化空调设计
  Purification Air Conditioning Design of GMP Workshop Purification CompanyGMP 2010采用欧盟净化级分类规则,根据实际消费情况分别设置A、B、C、D级。可根据净化空调设计中有关规定的详细要求停止选型。
  GMP 2010 adopts the classification rules of EU purification level, and sets A, B, C and D levels according to actual consumption situation. Selection can be stopped according to the detailed requirements of relevant regulations in the design of purified air conditioning.
  C/D区使用比较频繁的C类和D类区域均采用全风道空调系统。
  Full air duct air conditioning system is used in both C and D areas where C/D area is most frequently used.
  1.1.1
  1.1.1
  净化空调空气处理工艺空气处理的具体工艺流程如下:室外新风粗效过滤回风混面冷却风机增压加热介质过滤过滤进料进入室内。净化空调系统对空气的要求经过粗效率、中效率和率三个层次的过滤。组合式空调箱负责空气的粗效过滤、中效过滤及等焓加湿处理,空气的过滤由洁净区房间的过滤送风口完成。进入洁净区域的空气由室内回风口通过回风管道返回到组合空调箱的回风段。
  The specific process flow of air treatment in the air treatment process of purified air conditioning is as follows: outdoor fresh air coarse filtration return air mixing cooling fan pressurized heating medium filtration high efficiency filter feed into the indoor. The requirements of air purification and air conditioning system are filtered through three levels: coarse efficiency, medium efficiency and high efficiency. The combined air conditioning box is responsible for the crude, medium and equal enthalpy humidification of air. The efficient air filtration is accomplished by the efficient filter air supply outlet in the clean room. The air entering the clean area is returned to the return air section of the combined air conditioning box through the return air duct from the indoor return air outlet.
  对于不适合回风的房间,如带有湿热气体、粉尘分布的房间,应设置净化排气系统。返回空气和废气净化空调系统的风量应符合空气供应体积之间的压力差,确保相邻房间清洁水平不同的是10 Pa,而相邻的房间之间的压差与压差梯度相同的清洁水平要求是5。洁净室内的空气分配主要采用上送风侧和下送风(排气)方式。净化空调系统的空气处理单元采用双层金属保温墙板组合式空调单元,内外墙板均采用彩钢板。
  For rooms not suitable for return air, such as rooms with hot and humid gas, dust distribution, should be set up to purify the exhaust system. The air volume of return air and exhaust air purification air conditioning system should meet the pressure difference between air supply volume, ensuring that the cleaning level of adjacent rooms is 10 Pa, while the cleaning level requirement of the same pressure difference and pressure gradient between adjacent rooms is 5. The air distribution in the clean room mainly adopts the upper air supply side and the lower air supply (exhaust) mode. The air treatment unit of the purified air conditioning system adopts the combined air conditioning unit of double-layer metal thermal insulation wallboard, and the inner and outer wallboards are all made of coloured steel plates.
  1.1.2
  1.1.2
  空气变更请求
  Air change request
  丙级:夏季室内温度控制在20 ~ 24℃,夏季室内相对湿度控制在45% ~ 60%;冬季室内温度控制在18 ~ 22℃;冬季室内相对湿度控制在45% ~ 60%。通风频率25次/小时。
  Class C: indoor temperature in summer is controlled at 20-24 C, indoor relative humidity in summer is controlled at 45%-60%, indoor temperature in winter is controlled at 18-22 C, indoor relative humidity in winter is controlled at 45%-60%. Ventilation frequency is 25 times per hour.
  D:夏季室内温度控制在22 ~ 26℃,夏季室内相对湿度为45% ~ 65%;冬季室内温度控制在18 ~ 22℃;冬季室内相对湿度控制在45% ~ 65%。通风频率15次/小时。
  D: Indoor temperature in summer should be controlled at 22-26 C, relative humidity in summer should be 45%-65%, indoor temperature in winter should be controlled at 18-22 C, and indoor relative humidity in winter should be controlled at 45%-65%. Ventilation frequency is 15 times per hour.
  1.1.3
  1.1.3
  管
  tube
  风管制造数据采用镀锌钢板,风管保温数据采用闭孔海绵橡胶,灭火性能不好,燃烧等级为B级。
  The data of air duct manufacture are galvanized steel plate, and the data of air duct insulation are closed-hole sponge rubber. The fire extinguishing performance is not good, and the burning grade is B.
  1.1.4
  1.1.4
  一个特定操作区域或章节1.1.4.1的详细计划
  Detailed plan for a specific operating area or section 1.1.4.1洗衣区空气处理流程
  Air treatment process in laundry area
  至于洗衣区域,由于洗衣机设备的部分排风,排风量不断变化。从控制风量平衡和房间压差的角度考虑,该房间的排风应由另一排风支管停止,并设置排气阀。
  As for the laundry area, due to the partial exhaust of washing machine equipment, the exhaust volume is constantly changing. From the point of view of controlling air balance and room pressure difference, the exhaust of this room should be stopped by another exhaust branch pipe and set up exhaust valve.
  1.1.4.2
  1.1.4.2
  洗瓶、胶塞、铝盖清洗区域空气处理工艺方案设计,应考虑洗瓶、胶塞、铝盖清洗等技术设备排气量大。因此,当设备处于悬挂状态时,房间应采用回风路,并在回风管道上设置可变风量阀,以处理房间的风量平衡,节约能源。对应空调系统的风量和管道流量如图2所示。
  In the design of air treatment process for bottle washing, rubber stopper and aluminium cover cleaning area, large exhaust volume of technical equipment such as bottle washing, rubber stopper and aluminium cover cleaning should be considered. Therefore, when the equipment is suspended, the room should adopt the return air circuit and install variable air valve on the return air pipeline to deal with the air balance of the room and save energy. The air flow and pipeline flow of the corresponding air conditioning system are shown in Figure 2.
  1.2
  One point two
  B +空调系统
  B + Air Conditioning System
  区域B+A属于系统的中心区域,部分区域B+A的布置图如图3所示。对于这类面积,由于A类面积较大,且FFU运行过程中加热类比明显,可以从合理性的角度考虑以下处理方法。这种处理方法具有以下优点:
  Area B+A belongs to the central area of the system. The layout of part of area B+A is shown in figure 3. For this kind of area, because of the large area of Class A and obvious heating analogy during FFU operation, the following treatment methods can be considered from the perspective of rationality. This method has the following advantages:
  (1)采用固定风量阀,不会造成整个系统阻力不平衡;(2)采用电动关闭阀和FFU联锁,解决空调箱开启时FFU未开启时倒灌的问题;(3)采用层流送风机组处理FFU加热引起的负荷增加;(4)采用A级层流回风夹芯壁面侧吸,防止A级层流破坏B级环境的风险。
  (1) Fixed air flow valve will not cause unbalanced resistance of the whole system; (2) Electric shut-off valve and FFU interlock are used to solve the problem of backfilling when FFU is not opened when air conditioning box is opened; (3) Laminar flow fan unit is used to deal with the load increase caused by FFU heating; (4) A-level laminar return air sandwich wall side suction is used to prevent the risk of A-level laminar flow destroying B-level environment.
  值得注意的是,在采用该方案时,需要考虑房间大小是否能满足回程墙的大小和层间间距所需的空间。
  It is worth noting that when adopting this scheme, it is necessary to consider whether the room size can meet the size of the return wall and the space required for the interlayer spacing.
  空调水系统设计
  Design of Air Conditioning Water System
                               GMP车间净化公司
  普通空调冷源采用供冷冷水机组(7 ~ 12℃),原冷水冷却系统在冷水不足或没有冷水的情况下,也可采用空气冷却系统;空调用热水加热(50 ~ 60℃),达到平均温度的目的。蒸汽(0.2mpa)常用来给空调加湿。
  Ordinary air conditioning chillers use chillers (7 - 12 C). In the case of insufficient or no chilled water, the original chilled water cooling system can also use air cooling system. Hot water heating (50 - 60 C) is used for air conditioning to achieve the purpose of average temperature. Steam (0.2 mpa) is often used to humidify air conditioning.
  近年来,通过分析国外工程公司的设计方案,发现国外药品消费中心的系统设计倾向于采用纯蒸汽加湿。
  In recent years, by analyzing the design schemes of foreign engineering companies, it is found that the design of foreign drug consumption centers tends to adopt pure steam humidification.
  消防排烟系统设计在满足GMP(2010版)要求的前提下,空调的设计还应满足其他现有标准,主要是空调通风系统的消防排烟系统设计标准。
  On the premise of meeting the requirements of GMP (2010 edition), the design of fire fighting and smoke exhaust system should also meet other existing standards, mainly the design standards of fire fighting and smoke exhaust system of air conditioning and ventilation system.
  (1)所有空调通风系统的风机均与大厦火灾报警系统联锁。
  (1) Fans in all air conditioning and ventilation systems are interlocked with fire alarm systems in buildings.
  (2)风管通过防火墙、防火隔断、伸缩缝、楼板时,应配备防火阀,防火阀应与空调系统内所有通风空调设备联锁。当空调系统中的一个消防阀任意动作关闭时,系统中的所有通风和空调设备将暂停运行,同时系统将消防阀关闭的信号发送到消防中心,停止火灾报警。
  (2) When air ducts pass through firewalls, fire partitions, expansion joints and floors, they should be equipped with fire valves, which should be interlocked with all ventilation and air-conditioning equipment in the air-conditioning system. When a fire valve in the air conditioning system closes at will, all ventilation and air conditioning equipment in the system will be suspended. At the same time, the system will send the signal of the fire valve closing to the fire control center to stop the fire alarm.
  (3)消防排烟措施应尽量采用自然排烟方式。对于不能满足自然排烟要求的区域,应设置机械排烟系统。当发生火灾时,应启动相应区域的消防排烟系统,确保火灾现场人员的安全疏散。一般可设计2套机械排烟系统,一套用于走廊及外隔间排烟,另一套用于洁净区走廊排烟。洁净区走廊是地面封闭空间,需要设计一套排烟和送风系统。洁净区走廊排烟设备开启时,送风系统也随之开启。
  (3) Natural smoke exhaust should be adopted as far as possible in fire control and smoke exhaust measures. Mechanical smoke exhaust system should be set up in areas that can not meet the requirements of natural smoke exhaust. When a fire occurs, the fire fighting and smoke exhaust system in the corresponding area should be activated to ensure the safe evacuation of the fire scene personnel. Generally, two sets of mechanical smoke exhaust systems can be designed, one for smoke exhaust in corridors and compartments, and the other for smoke exhaust in corridors of clean areas. Clean area corridor is a ground enclosed space, which needs to design a set of smoke exhaust and air supply system. When the smoke exhaust equipment in the corridor of clean area is opened, the air supply system is also opened.
  (4)排烟系统主要由以下局部组成:排烟、排烟防火挡板和280℃防火挡板、排烟风机、排气管等。其中,排烟口通常是关闭的。火灾发生时,可通过火灾自动报警、安装联动打开排烟区的排烟口,并在现场设置手动开启安装备用。当系统中任何一个排烟口打开时,相应的排烟消防阀和排烟风机应相应联锁开启。此外,火灾排烟系统启动15秒内,应自动关闭与火灾排烟系统无关的区域所有通风空调系统,且排烟温度高于280℃,关闭排烟防火挡板。
  (4) The smoke exhaust system is mainly composed of the following parts: smoke exhaust, smoke exhaust fireproof baffle and 280 C fireproof baffle, smoke exhaust fan, exhaust pipe, etc. Among them, the exhaust nozzle is usually closed. When a fire occurs, the smoke outlet in the smoke exhaust area can be opened through automatic fire alarm and installation linkage, and manual opening and installation standby can be set up at the scene. When any exhaust outlet in the system is opened, the corresponding exhaust fire valve and exhaust fan should be interlocked. In addition, within 15 seconds of the start-up of the fire smoke exhaust system, all ventilation and air conditioning systems in areas unrelated to the fire smoke exhaust system should be automatically closed, and the smoke exhaust temperature is higher than 280 C, and the smoke exhaust and fire protection baffle should be closed.
  当本区域内所有排烟消防阀或排烟风机前排烟消防阀关闭时,排烟风机也将暂停运行。此外,消防排风机的安装及相关控制,应配备双路电源和应急电源。
  When all smoke exhaust fire valves or front smoke exhaust fire valves of smoke exhaust fans in the region are closed, the smoke exhaust fan will also be suspended. In addition, fire exhaust fan installation and related control should be equipped with dual power supply and emergency power supply.
  Py-01和02系统描述:
  Py-01 and 02 system description:
  (1)排烟口正常关闭。如遇火灾,可通过消防控制中心手动或远程打开。
  (1) Smoke outlets are normally closed. In case of fire, it can be opened manually or remotely through the fire control center.
  (2)排烟口与排烟风机联锁,打开任何排烟口及其对应的机械排烟机和排烟风机,打开前排烟防火阀。
  (2) The smoke outlet is interlocked with the smoke exhaust fan, any smoke outlet and its corresponding mechanical smoke exhaust machine and smoke exhaust fan are opened, and the front smoke fire valve is opened.
  (3)消防阀前排烟风机代替鼓风机进口(常闭)联锁,当温度达到280℃时关闭。
  (3) The smoke exhaust fan in front of the fire valve replaces the blower inlet (normally closed) interlock, and closes when the temperature reaches 280 C.
  (4)当所有的烟门店在系统关闭或风扇入口是前排(下降到50楼),系统和应用程序软件工具集成在一起,形成一个适当的MES管理软件系统的生物制药行业在中国国情。在此基础上,逐步建立数据管理(PDM / ERP) /企业信息资源管理、供应链管理(SCM),客户关系管理(CRM)和其他技术集成,提升企业的研发能力和管理水平,节能、产量和品质的进步,减少消费资本,推进售后服务质量,完成生物制药行业的设计企业,生产自动化,数字管理网络,资源密集,信息齐全,建立超越型。
  (4) When all tobacco stores are in the front row (down to the 50th floor) when the system is closed or the fan entrance is down, the system and application software tools are integrated to form an appropriate MES management software system for the biopharmaceutical industry in China. On this basis, the integration of data management (PDM/ERP)/enterprise information resources management, supply chain management (SCM), customer relationship management (CRM) and other technologies will be established step by step, so as to enhance the research and development ability and management level of enterprises, improve energy saving, output and quality, reduce consumption capital, promote after-sales service quality, complete the design enterprises, production automation, digital management network of the biopharmaceutical industry, and capital. Source-intensive, complete information, establish transcendental.
 